Home test chambers thermal shock test chambers TS40

thermal shock test chambers TS40


thermal shock test chambers TS40



  • Large-scale colored LCD touch dialogue microcomputer control system, operation is simple, running state is clear.
  • Friendly human-machine interface of controller, convenient program setting, complete abnormity and trouble-shooting display functions.
  • With RS-232 or RS-485 interface that can be connected with computer for remote control and convenient use.
  • In the running of preset starting time, it has functions of automatic precooling, preheating and stand-by.
  • Times of circulation and defrosting and automatic (manual ) defrosting can be set.
  • Fully-closed imported compressor + environment-friendly refrigerant, plate type cold and heat exchanger and two-stage cascade ultra low temperature refrigeration System.
  • Load wiring test components can be installed outside the test hole.
  • Three-chamber or two-chamber type can be selected.
  • Three-chamber type can be divided into three parts such as high temperature zone, low temperature zone and test zone, tested samples are put in test area in complete static state, special heat storage, cold storage structure and the way of forced switching of cold and hot air channel are used in introducing samples to test zone to finish high and low temperature shock test.
  • Three-chamber type can independently set functions under three different conditions of high temperature, .low temperature and thermal shock, when executing thermal shock conditions, functions of tank 2 and tank 3 can be selected, it also has the function of high and low temperature testing machine.
Features:

Standard Configuration

Model TS40 TS55
05 08 15 25 05 08 15 25
Performance
Experiment method Adopt pneumatic switching of air door and Three-chamber or two-chamber type
High temp.chamber Pre-heat temp. range 60~+200℃
Heat up time RT.→+200℃ Approx 35 min
Low temp. chamber Pre-cool temp. range -55℃ -65℃
Pull down time +20→-55℃ Approx 60min +20→-65℃ Approx 70min
Test chamber temp.  range -40℃ +150℃ -55℃+150℃
Temp. deviation ±2℃
Temp. recovery time Within 5 minutes
Recovery  term Exposure to high temperature Exposure to low temperature Exposure to high temperature Exposure to low temperature
150℃30min ­40℃30min 150℃30min 55℃ 30min
To restore conditions: room temperature of +20 ℃.
Composition
Exterior  material Stainless steel sus304
Interior  material Stainless steel( sus304)
Insulation  material Rigid polyurethane foam+glass fibre wool
Observation window Glass with a heat generator
Cable hole Inside diameter ¦µ50
Heater Iron-chrome wire heater
High temp.chamber Heater Iron-chrome wire heater
Motor Axial flow fan
Low temp. chamber Heater Iron-chrome wire heater
Cooler Finned heat exchanger, cold storage device.
Motor Centrifugal blower
Drive unit Pneumatic cylinder / Air compressor
Controller
Operation interface Touch screen type LCD Monitor
Temp. setting method Touch screen monitor
Temp. control method PID Controll
Operation function Fixed operation, Progrmmable operation
Sensor PT100Ω
Refrigeration System
Refrigerating method Hermetic compressor cascade refrigeration(air-cooled or water-cooled condenser)
Refrigerator Hermetic or semi-hermetic refrigerating compressor
Refrigerant R507+R23
Evaporator Finned heat exchanger
Safe Device
Independence overtemp. protection/over current breaker/ Refrigerator overload relay,refrigerator overpressure and overheat  protection/fuse-wire
Standard
Internal dimensions  (cm) D 35 40 50 60 35 40 50 60
W 40 50 60 70 40 50 60 70
H 35 40 50 60 35 40 50 60
External dimensions (cm) D 132 147 192 217 132 147 192 217
W 125 135 155 165 125 135 155 165
H 157 150 160 170 157 150 160 170
Internal capacity (L) 50 80 150 250 50 80 150 250
Power Supply AC 380±10%V 50±0.5 Hz
Power (kw) 16kw 25kw 30kw 40kw 22kw 30kw 35kw 47kw
Specimen weight 2.5kg 5kg 10kg 15kg 2.5kg 5kg 10kg 15kg
Accessories
Stainless steel shelves plate, 2pcs/cable hole lid(¦µ50),1pcs/chamber lamp,1pcs/ Product description, 1set
Optional  Accessories
Recorder


  • The performance shown here is the value under the condition of the ambient temperature of 23°C±2°C, humidity of 65%RH±20%. And there is not burden.
  • The projection is not included for Internal dimensions and External dimensions.
  • Temperature range including:-65~150℃